Install GridZeno on Solplanet hybrid.
For Solplanet, there's no cable from the GridZeno dongle to the inverter. It talks to Solplanet's Ai-Logger over your network with Modbus TCP on port 9999, which the Ai-Logger uses from the factory. The Ai-Logger is Solplanet's accessory, which is bought separately and connected to the inverter's RS485 port with a cable. The Ai-Dongle or Wi-Fi stick that comes with the inverter is only for Solplanet's app and cloud and can't be used for GridZeno.
- Applies to
- ASW H-S2, H-T2, H-T3, H-T2/T3-DG, SH and TH with Ai-Logger
- Connection
- Over your network, without a cable to the inverter
- Time
- About 15 minutes
Through the Ai-Logger, GridZeno shows the solar production and lowers the inverter's output at negative prices. The battery can only be read and controlled with the dongle connected directly to the inverter. What GridZeno can do on Solplanet hybrid
How the dongle recognises it: The model name in input 1018-1025 starts with ASW or SOL, and the model code 11-16 in 31073 is a hybrid.
What you need
- GridZeno Dongle
- The device ID is on the label, e.g. GZ-A1B2C3.
- Ai-Logger with software 003R or newer
- Connected to the inverter's Monitor port. The version is shown on the Ai-Logger's own page.
- Access to your router
- To find the Ai-Logger's IP address.
- USB power
- A 5 V USB charger and a cable with USB-C.
The connection
Solplanet's own logger, which is connected to the inverter's RS485 port Monitor (on the TH: Third_485) and to your network. The GridZeno dongle only needs power and network.
- Connection
- Solplanet Ai-Logger (Modbus TCP, port 9999)
Settings
On Solplanet Ai-Logger
- Modbus TCP port on the Ai-Logger
- 9999, as from the factory
- Slave ID
- 239 is used automatically
In GridZeno's Welcome
The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.
- Manufacturer and model
- Solplanet, Hybrid
- Connection
- Through Solplanet's Ai logger
- The Ai logger's address on your network
- The Ai-Logger's IP address.
Step by step
Each step has a small drawing that shows what to do.
- 1Check the Ai-Logger's port
Open the Ai-Logger's own page, and go to System settings, Communication settings and Network settings. Under Modbus TCP Port, the port must be 9999, which Solplanet states is the default. If it's set to something else, choose User-define Port, enter 9999, press Submit, and wait 10 seconds.
- 2Find the Ai-Logger's IP address
Find the Ai-Logger in your router's list of devices, and give it a fixed IP address so it doesn't change.
- 3Connect power to the dongle
Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.
- 4Connect the dongle to the network
Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, and enter the password. Over cable (LAN): plug a network cable from the router into the dongle's network port. The dongle must be on the same network as the Ai-Logger.
- 5The GridZeno dongle talks to the Ai-Logger
There's no cable between them. They meet in your router, and the GridZeno dongle queries the Ai-Logger every few seconds with Modbus TCP on port 9999. The Ai-Logger itself reads the inverter over RS485.
- 6Log in to GridZeno
Log in to GridZeno. Welcome pairs the dongle with its device ID and then asks about your inverter.
- 7Choose your inverter in Welcome
Choose your inverter, Solplanet Hybrid, and the connection Through Solplanet's Ai logger. Enter the Ai logger's IP address in the field The Ai logger's address on your network, and press Save inverter. The dongle then fetches its setup and reads from the inverter.
The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.
Take care
What GridZeno can control on Solplanet hybrid, and how, is on the page about Solplanet hybrid. If you're stuck, write to us with the model name.
Source
Ports, pins and menus are from the manufacturer's own manual: Solplanet UM0058 Ai-logger Modbus TCP (EN, V03 2024-04) and the user manuals for ASW H-S2, H-T2/T3, H-T2/T3-DG, SH and TH, Section 1, Brief introduction, and section 3, Application Notes.