100 days Free returns on the GridZeno Dongle. Try it on your own system. If it doesn't fit, we take it back and pay the shipping.
Installation · Solplanet

Install GridZeno on Solplanet hybrid with RS485 cable.

Solplanet's hybrid inverters have an RJ45 port for monitoring from other manufacturers, Monitor (on the TH: Third_485). Here the GridZeno dongle talks directly to the inverter with Modbus RTU, without an Ai-Logger. A is on pin 1, B on pin 2 and GND on pin 3, so the cable is made with only the three wires that are needed.

Needs an electrician: the inverter has to be opened
The inverter has to be opened to reach the port. This should be done by a qualified person, such as an authorised electrician.
Applies to
ASW H-T2, H-T3, H-T2/T3-DG, SH 8-10 kW and TH
Connection
Network cable with RJ45 plug
Time
About 30 minutes

The battery is controlled with the inverter's operating mode. The dongle saves your own mode and puts it back afterwards. What GridZeno can do on Solplanet hybrid with RS485 cable

How the dongle recognises it: The storage block from input 1600 can be read, so it's a hybrid. The battery is there when 1606 is 0x000A, and a second battery when 31740 is 0x000A.

GridZeno Dongle for Solplanet hybrid with RS485 cable

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
A shielded network cable, re-crimped at the inverter end with only three wires.
RJ45 plug and crimping tool
For the inverter end.
Screwdriver
For the communication cover's four M4 screws.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

On the communication board behind the inverter's communication cover. On the H-T2 and H-T3 it is RJ45 port 3 (COM2), on the DG port 3 just above the TCP/IP port, on the SH 8-10 kW CN707, which the cable reaches through the cable gland COM1 behind the lower front cover, and on the TH CN407 (COM3).

Port
Monitor (on the TH: Third_485)
Pin 1: A, RS485A, blue wire.
Pin 2: B, RS485B, white/blue wire.
Pin 3: GND, GND, white/green wire.
Pin 4: not in use.
Pin 5: not in use.
Pin 6: not in use.
Pin 7: not in use.
Pin 8: not in use.
The Monitor port, as Solplanet numbers the pins. Pins 1 and 2 are for monitoring from other manufacturers, pin 3 is GND. The plug shown with the contacts facing you and the locking tab at the back: pin 1 is furthest to the left.
  • Pin 1 A, RS485A
  • Pin 2 B, RS485B
  • Pin 3 GND, GND
03

The cable

A network cable where the inverter end is crimped with only three wires: the dongle's A on pin 1, B on pin 2 and GND on pin 3. The other positions in the connector are empty. An ordinary straight cable doesn't work here.

From the dongle to the inverter
Dongle endInverter end
Dongle pin 4, blue (A)Solplanet pin 1, RS485A
Dongle pin 5, white/blue (B)Solplanet pin 2, RS485B
Dongle pin 3, white/green (GND)Solplanet pin 3, GND
The other wiresCut off and insulated
04

Settings

On the inverter

Modbus address
Solplanet's Modbus protocol uses address 3 from the factory. The manuals mention neither address nor baud rate. On the DG, the address can be changed in the Solplanet app under Inverter configuration, Modbus address modification.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
Solplanet, Hybrid (RS485)
Connection
By cable (RS485)
RS485 settings
Keep the default GridZeno suggests for Solplanet (address 3).
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Turn off, and open the communication cover

    Switch off the AC breaker, and lock it. Set the DC switch to OFF, and lock it. Wait until the LEDs are off. Unscrew the communication cover's four M4 screws. On the SH 8-10 kW, you open the lower front cover instead.

  2. 2
    Pass the cable through the cable gland

    Cut off the connector at the inverter end, and pass the cable through a cable gland in the cover. Leave the plug in the holes you don't use.

  3. 3
    Crimp the inverter end with three wires

    Crimp on a new connector with blue (A) on pin 1, white/blue (B) on pin 2 and white/green (GND) on pin 3. The other wires are cut off and insulated.

  4. 4
    Plug the connector into Monitor

    Press the connector into the Monitor port until it clicks. On the TH, the port is called Third_485. The ports beside it are for parallel operation and battery.

  5. 5
    Close the cover again

    Screw the cover tight, and tighten the cable gland so the cable is sealed.

  6. 6
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  7. 7
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  8. 8
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  9. 9
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Solplanet Hybrid (RS485), and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

The Ai-Logger uses the same Monitor port. If you have an Ai-Logger, use the guide for the Ai-Logger instead. The Ai-Dongle in its own port can stay in place.
Never plug the cable into ports for parallel operation, BMS or TCP/IP. On the SH 8-10 kW, the network port CN704 carries 3.3 V on pins 4 and 5.
Solplanet doesn't describe the baud rate in the manuals. If the inverter doesn't respond, write to us with the inverter's software version.
The inverter must be opened. This should be done by a qualified person, for example an authorised installer.

What GridZeno can control on Solplanet hybrid with RS485 cable, and how, is on the page about Solplanet hybrid with RS485 cable. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: Solplanet UM0035 ASW H-T2/T3, UM0057 ASW H-T2/T3-DG, UM0060 ASW SH 8-10 kW and UM0063 ASW TH User Manuals (EN), The section on communication ports (the pin table for Monitor and Third_485) and 9.1, shutdown.