Installation · Solplanet

Install GridZeno on Solplanet ASW grid inverter with RS485 cable.

Solplanet's grid inverters without a battery have RS485 in an RJ45 port, COM. Here the GridZeno dongle talks directly to the inverter with Modbus RTU, without an Ai-Logger. A is on pin 1, B on pin 2 and GND on pin 4, so the cable is made with only the three wires that are needed. The energy meter has its own port.

Applies to
ASW S-G2, 5-10k-S, LT-G2, LT-G2-Pro, 25-40K-LT-G3, 40-50K-LT-G2 Pro, ASW-T and ASW-S
Connection
Network cable with RJ45 plug
Time
About 25 minutes

A grid inverter without a battery. GridZeno shows the solar production and lowers the inverter's output at negative prices. What GridZeno can do on Solplanet ASW grid inverter with RS485 cable

How the dongle recognises it: No storage block from input 1600, or the model code 1-5 in 31073: a grid inverter. The dongle doesn't tell the series apart; input 1000 says whether it's three-phase.

GridZeno Dongle for Solplanet ASW grid inverter with RS485 cable

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
A shielded network cable (Cat5e), re-crimped at the inverter end with only three wires.
RJ45 plug and crimping tool
For the inverter end. The waterproof RS485 connector is in the accessory bag or is available as an accessory.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

On the underside of the inverter under a cap or a cover. On the LT-G2 and LT-G3 there are two RJ45 ports, COM1 and COM2, with the same pins. The Wi-Fi stick and the energy meter each have their own port.

Port
COM (RJ45, RS485)
Pin 1: A, TX_RS485A, blue wire.
Pin 2: B, TX_RS485B, white/blue wire.
Pin 3: not in use.
Pin 4: GND, GND, white/green wire.
Pin 5: not in use.
Pin 6: not in use.
Pin 7: Power, +7V on ASW-T and ASW-S.
Pin 8: Power, +7V on ASW-T and ASW-S.
The COM port, as Solplanet numbers the pins. Pin 1 is A, pin 2 is B and pin 4 GND. On the ASW-T and the older ASW-S, pins 7 and 8 carry 7 V. The plug shown with the contacts facing you and the locking tab at the back: pin 1 is furthest to the left.
  • Pin 1 A, TX_RS485A
  • Pin 2 B, TX_RS485B
  • Pin 4 GND, GND
  • Pin 7 Must not be connected, +7V on ASW-T and ASW-S
  • Pin 8 Must not be connected, +7V on ASW-T and ASW-S
03

The cable

A network cable where the inverter end is crimped with only three wires: the dongle's A on pin 1, B on pin 2 and GND on pin 4. The other positions in the connector are empty. An ordinary straight cable doesn't work here.

From the dongle to the inverter
Dongle endInverter end
Dongle pin 4, blue (A)Solplanet pin 1, TX_RS485A
Dongle pin 5, white/blue (B)Solplanet pin 2, TX_RS485B
Dongle pin 3, white/green (GND)Solplanet pin 4, GND
The other wiresCut off and insulated, especially those on pins 7 and 8
04

Settings

On the inverter

Modbus address
Solplanet's Modbus protocol uses address 3 from the factory. The manuals mention neither address nor baud rate.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
Solplanet, ASW (RS485)
Connection
By cable (RS485)
RS485 settings
Keep the default GridZeno suggests for Solplanet (address 3).
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Pass the cable through the waterproof connector

    Turn off the inverter first: switch off the AC breaker and lock it, set the DC switch to OFF and lock it, and wait until the LEDs are off. Cut off the connector at the inverter end, and pass the cable through the waterproof RS485 connector or the cover's M25 cable gland.

  2. 2
    Crimp the inverter end with three wires

    Crimp on a new connector with blue (A) on pin 1, white/blue (B) on pin 2 and white/green (GND) on pin 4. The other wires are cut off and insulated, especially those on pins 7 and 8.

  3. 3
    Plug the connector into COM

    Unscrew the cap from the COM port, press the connector in until it clicks, and tighten the waterproof connector. On the LT-G2 and LT-G3 you can use COM1 or COM2.

  4. 4
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  5. 5
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  6. 6
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  7. 7
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Solplanet ASW (RS485), and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

On the ASW-T and the older ASW-S, pins 7 and 8 in the COM port carry 7 V. Solplanet states that wrong connections can damage the inverter.
If the inverter uses RS485 for a Wi-Fi stick that follows several inverters, or for an Ai-Logger or AiCom, use the guide for the Ai-Logger instead. There can only be one controller on RS485.
On the 40-50K-LT-G2 Pro, the DIP switch for the termination resistor must be set to ON if the inverter is the last on the cable.
The energy meter has its own port. Don't plug the cable into it. Solplanet doesn't describe the baud rate in the manuals. If the inverter doesn't respond, write to us.

What GridZeno can control on Solplanet ASW grid inverter with RS485 cable, and how, is on the page about Solplanet ASW grid inverter with RS485 cable. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: Solplanet UM0023 ASW S-G2, UM0012 ASW 5-10k, UM0005 LT-G2, UM0014 LT-G2-Pro, UM0016 LT-G3 25-40K, 40-50K-LT-G2 Pro, UM0006 ASW-T and UM0009 ASW-S User Manuals (EN), The pin table for the RJ45 port COM (RS485) and the section on fitting the RS485 cable.