Installation · SolaX

Install GridZeno on SolaX X3-Ultra / X3-AELIO.

X3-Ultra and the larger X3-AELIO are SolaX's three-phase hybrid inverters with a battery. The communication ports are gathered in the COM 1 connector, six RJ45 ports in one holder. The dongle goes in the RS485 port, where SolaX has set pins 1, 2, 7 and 8 aside for equipment from other manufacturers. There's no GND in the port, so the cable is made with only two wires.

Applies to
X3-ULT-15K to 30K, X3-ULT-10K/15K-GLV and X3-AELIO-36K to 61K
Connection
Network cable with RJ45 plug
Time
About 30 minutes

An X3-AELIO is controlled with SolaX' remote control, which stops by itself if the dongle goes silent. GridZeno can read an X3-Ultra but not control it yet. What GridZeno can do on SolaX X3-Ultra / X3-AELIO

How the dongle recognises it: X3-Ultra: the serial number starts with H3BC, H3BD, H3BF or H3BG. X3-AELIO: the serial number starts with 8021 and is read as GEN5.

GridZeno Dongle for SolaX X3-Ultra / X3-AELIO

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
A network cable that's re-crimped at the inverter end with only two wires.
RJ45 plug and crimping tool
For the inverter end. RJ45 plugs come in the inverter's accessory bag.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

On the underside of the inverter. COM 1 is a connector with six RJ45 ports in a cable holder: Parallel-1, Parallel-2, BMS-1, BMS-2, RS485 and DRM. The RS485 port is marked on the holder.

Port
RS485 in COM 1
Pin 1: A, REMOTE_485A, blue wire.
Pin 2: B, REMOTE_485B, white/blue wire.
Pin 3: SolaX accessories, PARALLEL_485AA.
Pin 4: SolaX accessories, PARALLEL_485AA.
Pin 5: SolaX accessories, PARALLEL_485BB.
Pin 6: SolaX accessories, PARALLEL_485BB.
Pin 7: A, REMOTE_485A.
Pin 8: B, REMOTE_485B.
The RS485 port in COM 1, with the pins numbered as SolaX numbers them. Pins 1 and 2 are for equipment from other manufacturers, pins 3 to 6 for SolaX's own accessories. On X3-AELIO, pins 3 and 6 aren't connected. The plug shown with the contacts facing you and the locking tab at the back: pin 1 is furthest to the left.
  • Pin 1 A, REMOTE_485A
  • Pin 2 B, REMOTE_485B
03

The cable

A network cable where the inverter end is crimped with only two wires: the dongle's A on pin 1 and B on pin 2. The rest of the positions in the plug are empty. An ordinary straight cable doesn't work here. The cable has to go through the COM 1 connector's coupling nut before the plug is crimped on.

From the dongle to the inverter
Dongle endInverter end
Dongle pin 4, blue (A)SolaX pin 1, REMOTE_485A
Dongle pin 5, white/blue (B)SolaX pin 2, REMOTE_485B
The other wiresCut off and insulated
04

Settings

On the inverter

Menu > Setting > Advance Setting > Modbus
Read off Baud Rate and Address. The dongle must have the same. The manual shows 19200 and 1 on X3-Ultra and 9600 and 1 on X3-AELIO.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
SolaX, X3-Ultra
Connection
By cable (RS485)
RS485 settings
The same baud rate and address as the inverter, 8N1. If the inverter is set to 19200, set 19200 on the dongle. X3-AELIO is set to 9600 at the factory.
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Read the baud rate and address

    In the display, go to Menu, Setting, Advance Setting, Modbus. It requires the installer code, which is 2014 from the factory. Note down Baud Rate and Address: the dongle must have the same.

  2. 2
    Remove the COM 1 connector

    Hold the latches on both sides of the COM 1 connector, and pull it out of the inverter. Unscrew the coupling nut, and take out a sealing plug.

  3. 3
    Pass the cable through the connector's parts

    Pass the cable through the coupling nut, the sealing bush and the connector housing, in that order. Leave the plugs in the holes you aren't using.

  4. 4
    Crimp the inverter end with two wires

    Cut off the plug at the inverter end. Crimp a new plug on with blue (A) on pin 1 and white/blue (B) on pin 2. The other wires are cut off and insulated.

  5. 5
    Plug it into RS485

    Press the RJ45 plug into the position marked RS485 in the cable holder until it clicks.

  6. 6
    Put the COM 1 connector back in

    Plug the COM 1 connector into the inverter until it clicks, and pull gently on the cable to check that it's secure. Tighten the coupling nut.

  7. 7
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  8. 8
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  9. 9
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  10. 10
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, SolaX X3-Ultra, and the connection By cable (RS485). Set the inverter's baud rate and address under RS485 settings. Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

Use only the RS485 port in COM 1. Parallel-1 and Parallel-2 are for other inverters, BMS-1 and BMS-2 for the battery, and the energy meter is in COM 2.
Parallel-1 and Parallel-2 have power on pin 3 (EPSBOX_RELAY_VCC), and DRM has +3.3 V on pin 5. Never plug the dongle's cable into them.
Pins 3 to 6 in RS485 are for SolaX's own accessories, such as Adapter Box G2, EV-Charger and DataHub. If there's already a cable in RS485, write to us before you connect the dongle.
The DONGLE port is for SolaX's own monitoring dongle. It isn't an RS485 port.
The cable to RS485 may be no more than 30 metres long.

What GridZeno can control on SolaX X3-Ultra / X3-AELIO, and how, is on the page about SolaX X3-Ultra / X3-AELIO. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: SolaX X3-ULTRA 15-30 kW and 10K/15K-GLV User Manual, version 16.0 (2026-07-30), and X3-AELIO User Manual (EN), Sections 8.6.1, Pin Assignment of COM 1 Port, 8.6.4, RS485 Communication Connection, and 10.7.2, Advanced Setting (Setting Modbus).