Installation · Growatt

Install GridZeno on Growatt MIN 7000-10000TL-X.

The large MIN inverters, 7000 to 10000 W, have only one signal connector, COM, and it comes as 4-pin or 16-pin. The dongle is connected with two wires to RS485A1 and B1, which Growatt uses for monitoring: pins 1 and 2 in the 4-pin connector, pins 3 and 4 in the 16-pin one.

Applies to
MIN 7000-10000TL-X, TL-X(E) and TL-X2
Connection
Wires in the inverter's terminal plug
Time
About 30 minutes

A grid inverter without a battery. GridZeno shows solar, consumption and grid and lowers the inverter's export limit at negative prices. What GridZeno can do on Growatt MIN 7000-10000TL-X

How the dongle recognises it: The same series as the MIN TL-X for the dongle: the type code 5201, or 5200 when the range from 3000 answers.

GridZeno Dongle for Growatt MIN 7000-10000TL-X

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
GridZeno's Modbus cable with one end cut off, or another network cable with one plug.
Wire strippers and ferrules
Two ferrules for the two wires in the connector.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

The round connector marked COM on the underside between the PV inputs and USB. The same connector is used for the energy meter, so there may already be wires in it.

Port
COM (4- or 16-pin connector)
Pin 1: Relay, +12V.
Pin 2: Relay, COM.
Pin 3: A, RS485A1, blue wire.
Pin 4: B, RS485B1, white/blue wire.
Pin 5: not in use.
Pin 6: not in use.
Pin 7: Meter, RS485B2.
Pin 8: Meter, RS485A2.
Pin 9: not in use.
Pin 10: not in use.
Pin 11: not in use.
Pin 12: not in use.
Pin 13: DRM, RefGen.
Pin 14: not in use.
Pin 15: Current clamp, CT-P.
Pin 16: Current clamp, CT-N.
The 16-pin COM connector seen from the wire side, with Growatt's pin numbering. RS485A1 and B1 on pins 3 and 4 are for monitoring. If you have the 4-pin connector, it's pins 1 and 2. The numbers are on the plug.
  • Pin 3 A, RS485A1
  • Pin 4 B, RS485B1
03

The cable

A network cable with an RJ45 plug for the dongle at one end and the other end cut off. At the inverter end, only the two wires from pins 4 and 5 are used, with ferrules on.

From the dongle to the inverter
Dongle endInverter end
Pin 4, blue (A)COM RS485A1: pin 3 (16-pin) or pin 1 (4-pin)
Pin 5, white/blue (B)COM RS485B1: pin 4 (16-pin) or pin 2 (4-pin)
The other wiresCut off and insulated
04

Settings

On the inverter

Set parameter > General > Set Comaddr
001, as from the factory
Modbus
Modbus RTU at 9600 baud, 8N1. That's what the dongle uses from the factory, so there's nothing to set.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
Growatt, MIN
Connection
By cable (RS485)
RS485 settings
Keep the default: 9600 baud, 8N1, address 1.
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Check the address

    Press the touch button once to scroll, and twice to select. Go to Set parameter, General and Set Comaddr. It should be set to 001, as from the factory.

  2. 2
    Unplug the COM connector

    Switch off the inverter first: turn off the AC breaker, and set the DC switch to OFF. The round connector marked COM is on the underside between the PV inputs and USB. Press the catches in, and pull it out, preferably with the removal tool from the accessory bag. Check whether it is 4-pin or 16-pin.

  3. 3
    Prepare the cable

    Pass the cable through the connector's pressure screw, sealing ring and threaded sleeve. Strip the two wires from pin 4 (blue) and pin 5 (white/blue), and fit ferrules. Insulate the other wires.

  4. 4
    The 16-pin connector: pins 3 and 4

    Blue (A) goes in pin 3 and white/blue (B) in pin 4, following the numbers on the connector. Don't touch wires in pins 7 and 8: they belong to the energy meter.

  5. 5
    The 4-pin connector: pins 1 and 2

    Blue (A) goes in pin 1 and white/blue (B) in pin 2, following the numbers on the connector. Pins 1 and 2 are at the bottom. Don't touch wires in pins 3 and 4: they belong to the energy meter.

  6. 6
    Plug the connector back in

    Push the threaded sleeve into the connector, and tighten the cap. Press the connector into COM until it clicks and sits firmly.

  7. 7
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  8. 8
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  9. 9
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  10. 10
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Growatt MIN, and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

RS485A2 and B2 in the same connector are the energy meter's connection: pins 3 and 4 in the 4-pin connector and pins 7 and 8 in the 16-pin one. They must not be moved or connected to anything else.
Be careful: on the large MIN, A1 and B1 are the monitoring and A2 and B2 the energy meter. On the small MIN it's the other way round.

What GridZeno can control on Growatt MIN 7000-10000TL-X, and how, is on the page about Growatt MIN 7000-10000TL-X. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: Growatt MIN 7000-10000TL-X User Manual (EN, 2021-10) and MIN 7-10K TL-X2 User Manual (GR-UM-292-A-00), Section 3.1, Overview, 6.5, Signal connector, with figures 6.10-6.12, 7.2.2, Set inverter COM address, and 7.4.1, RS485.