Install GridZeno on Solplanet 75-125K-LT with RS485 cable.
The large ASW75-125K-LT have two RS485 connectors, COM2 and COM3. Solplanet has set COM2 aside for equipment from other manufacturers, so the Ai-Dongle in COM1 and any chain on COM3 can stay in place. The GridZeno dongle is connected with three wires in the COM2 connector.
- Applies to
- ASW75K, 80K, 100K, 110K and 125K-LT
- Connection
- Wires in the inverter's terminal plug
- Time
- About 30 minutes
A grid inverter without a battery. GridZeno shows the solar production and lowers the inverter's output at negative prices. What GridZeno can do on Solplanet 75-125K-LT with RS485 cable
How the dongle recognises it: No storage block from input 1600, or the model code 1-5 in 31073: a three-phase grid inverter. The dongle treats it like the other ASW grid inverters.
What you need
- GridZeno Dongle
- The device ID is on the label, e.g. GZ-A1B2C3.
- Cable
- GridZeno's Modbus cable with one end cut off, or another twisted cable with three conductors.
- Ferrules and crimping tool
- Wire ferrules for the three wires.
- Torque screwdriver
- The terminals are tightened to 1.2 Nm.
- USB power
- A 5 V USB charger and a cable with USB-C.
The port
On the underside of the inverter by COM1 (Ai-Dongle) and COM3. The connector is a waterproof connector with an 8-pin screw terminal inside.
- Port
- COM2 (8-pin connector, for 3rd party)
- Pin 3 A, RS485A
- Pin 4 B, RS485B
- Pin 2 GND, GND_SELV
- Pin 1 Must not be connected, +8VA_SELV
- Pin 5 Must not be connected, +8VA_SELV
The cable
A network cable with an RJ45 plug for the dongle at one end and the other end cut off. At the inverter end, only the three wires from pins 4, 5 and 3 are used, with ferrules fitted.
| Dongle end | Inverter end |
|---|---|
| Dongle pin 4, blue (A) | COM2 pin 3, RS485A |
| Dongle pin 5, white/blue (B) | COM2 pin 4, RS485B |
| Dongle pin 3, white/green (GND) | COM2 pin 2, GND_SELV |
| The other wires | Cut off and insulated |
Settings
On the inverter
- Modbus address
- Solplanet's Modbus protocol uses address 3 from the factory. The manual mentions neither address nor baud rate.
In GridZeno's Welcome
The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.
- Manufacturer and model
- Solplanet, ASW (RS485)
- Connection
- By cable (RS485)
- RS485 settings
- Keep the default GridZeno suggests for Solplanet (address 3).
Step by step
Each step has a small drawing that shows what to do.
- 1Switch off, and remove the COM2 connector
Switch off the AC breaker, and lock it. Set the DC switch to OFF, and lock it. Wait until the LEDs have gone out. Take the dust cover off COM2, or press the connector's lock, and pull it out.
- 2Pass the cable through the connector's parts
Unscrew the nut, take out the sealing ring and the insert, and pass the cut end of the cable through the nut and the seal.
- 3Prepare the cable
Strip 33 mm of the sheath and 7.5 mm of the three wires from pin 4 (blue), pin 5 (white/blue) and pin 3 (white/green), and crimp ferrules on. Insulate the other wires.
- 4Screw the wires into pins 3, 4 and 2
Blue (A) goes in pin 3, white/blue (B) in pin 4 and white/green (GND) in pin 2. Tighten to 1.2 Nm. Pins 1 and 5 carry 8 V: don't touch them. Solplanet draws the bottom row in two directions, so follow the numbers on the connector itself.
- 5Plug the connector into COM2
Assemble the connector, screw the nut on, and press the connector into COM2 until it clicks. If the inverter is the last one on the cable, set the DIP switch for the terminating resistor to ON.
- 6Plug the RJ45 end into the dongle
The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.
- 7Connect power to the dongle
Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.
- 8Connect the dongle to the network
Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.
- 9Log in, and choose your inverter
Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Solplanet ASW (RS485), and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.
The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.
Take care
What GridZeno can control on Solplanet 75-125K-LT with RS485 cable, and how, is on the page about Solplanet 75-125K-LT with RS485 cable. If you're stuck, write to us with the model name.
Source
Ports, pins and menus are from the manufacturer's own manual: Solplanet UM0030 ASW75K-110K-LT (EN, V06) and UM0066 ASW125K-LT (EN, V01) User Manuals, The section on RS485 in COM2 and COM3 (the pin table and the DIP switch) and fitting the RS485 connector.