Install GridZeno on Solplanet 45-60K-LT-G3 with RS485 cable.
The ASW45-60K-LT-G3 doesn't have RJ45 for RS485, but two 3-pin screw terminals in COM2, marked A, B and G. Here the GridZeno dongle talks directly to the inverter with Modbus RTU, without an Ai-Logger. The dongle is connected with three wires.
- Applies to
- ASW45K, 50K and 60K-LT-G3
- Connection
- Wires in the inverter's terminal plug
- Time
- About 30 minutes
A grid inverter without a battery. GridZeno shows the solar production and lowers the inverter's output at negative prices. What GridZeno can do on Solplanet 45-60K-LT-G3 with RS485 cable
How the dongle recognises it: No storage block from input 1600, or the model code 1-5 in 31073: a three-phase grid inverter. The dongle treats it like the other ASW grid inverters.
What you need
- GridZeno Dongle
- The device ID is on the label, e.g. GZ-A1B2C3.
- Cable
- GridZeno's Modbus cable with one end cut off, 3 to 5.5 mm thick.
- Wire stripper and screwdriver
- For the terminals and the AC/COM cover's M4 screws.
- USB power
- A 5 V USB charger and a cable with USB-C.
The port
Behind the AC/COM cover on the inverter. COM3 and COM4 next to it are RJ45 ports for control by the grid company, not RS485.
- Port
- COM2 (terminals A, B and G)
- Pin 1 A, A
- Pin 2 B, B
- Pin 3 GND, G
The cable
A network cable where one end has an RJ45 connector for the dongle and the other end is cut off. At the inverter end, only the three wires from pins 4, 5 and 3 are used.
| Dongle end | Inverter end |
|---|---|
| Dongle pin 4, blue (A) | COM2 pin 1 (terminal A) |
| Dongle pin 5, white/blue (B) | COM2 pin 2 (terminal B) |
| Dongle pin 3, white/green (GND) | COM2 pin 3 (terminal G) |
| The other wires | Cut off and insulated |
Settings
On the inverter
- Modbus address
- Solplanet's Modbus protocol uses address 3 from the factory. The manual mentions neither address nor baud rate.
In GridZeno's Welcome
The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.
- Manufacturer and model
- Solplanet, ASW (RS485)
- Connection
- By cable (RS485)
- RS485 settings
- Keep the default GridZeno suggests for Solplanet (address 3).
Step by step
Each step has a small drawing that shows what to do.
- 1Turn off, and open the AC/COM cover
Switch off the AC breaker, and lock it. Set the DC switch to OFF, and lock it. Wait until the LEDs are off. Unscrew the AC/COM cover's M4 screws.
- 2Pass the cable through the cable gland
Unscrew the cable gland's nut, take out the seal and the plug, and pass the cut end of the cable through.
- 3Prepare the cable
Strip 8 mm from the three wires from pin 4 (blue), pin 5 (white/blue) and pin 3 (white/green). Insulate the other wires.
- 4Screw the wires into A, B and G
Blue (A) goes in terminal A, white/blue (B) in terminal B and white/green (GND) in terminal G. If the inverter is the last one on the cable, set the DIP switch for the terminating resistor to ON.
- 5Close the cover again
Screw the AC/COM cover on with 1.6 Nm, and tighten the cable gland.
- 6Plug the RJ45 end into the dongle
The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.
- 7Connect power to the dongle
Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.
- 8Connect the dongle to the network
Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.
- 9Log in, and choose your inverter
Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Solplanet ASW (RS485), and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.
The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.
Take care
What GridZeno can control on Solplanet 45-60K-LT-G3 with RS485 cable, and how, is on the page about Solplanet 45-60K-LT-G3 with RS485 cable. If you're stuck, write to us with the model name.
Source
Ports, pins and menus are from the manufacturer's own manual: Solplanet UM0036 ASW45K-60K-LT-G3 User Manual (EN, V04), The section on RS485 in COM2 (terminals A, B and G and the DIP switch) and COM3/COM4.