Installation · SolaX

Install GridZeno on SolaX X1-HYB-LV-EU.

X1-HYB-LV-EU is SolaX's single-phase hybrid inverter for a 48 V battery. It has no RJ45 port for external control. The dongle is connected with three wires in the 30-pin COM connector: pins 5 and 6, which SolaX calls REMOTE_485A and REMOTE_485B, and GND on pin 26.

Applies to
X1-HYB-3.0 to 6.0-LV-EU
Connection
Wires in the inverter's terminal plug
Time
About 30 minutes

What GridZeno can do on SolaX X1-HYB-LV-EU today

There's no public register map for the X1-HYB-LV-EU, so the dongle can't read it yet.

  • Live overview of solar, consumption and gridAll subscriptions
    Coming later
  • Battery state of chargeAll subscriptions
    Coming later
  • Stop selling at negative pricesSmart and Pro
    Coming later
  • Charge from the grid when power is cheapSmart and Pro
    Coming later
  • Discharge the battery when power is expensivePro
    Coming later

You can connect the dongle by this guide, but it reads nothing from the inverter until its firmware can. GridZeno Dongle for SolaX X1-HYB-LV-EU

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
GridZeno's Modbus cable with one end cut off, or another network cable with one plug.
Ferrules and crimping tool
Wire ferrules for 0.5 to 0.75 mm² wire.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

The round, waterproof COM connector on the underside of the inverter. The same connector is used for the energy meter, current clamp and battery, so there may already be wires in it.

Port
COM (30-pin connector)
Pin 1: not in use.
Pin 2: not in use.
Pin 3: not in use.
Pin 4: not in use.
Pin 5: A, REMOTE_485A, blue wire.
Pin 6: B, REMOTE_485B, white/blue wire.
Pin 7: Meter, METER_485A.
Pin 8: Meter, METER_485B.
Pin 9: Current clamp, CT1_1.
Pin 10: Current clamp, CT1_2.
Pin 11: not in use.
Pin 12: not in use.
Pin 13: not in use.
Pin 14: not in use.
Pin 15: not in use.
Pin 16: not in use.
Pin 17: Battery, BMS_485B.
Pin 18: Battery, BMS_485A.
Pin 19: Battery, BMS_GND.
Pin 20: not in use.
Pin 21: not in use.
Pin 22: not in use.
Pin 23: not in use.
Pin 24: not in use.
Pin 25: not in use.
Pin 26: GND, GND_COM, white/green wire.
Pin 27: Battery, BMS_CANH.
Pin 28: Battery, BMS_CANL.
Pin 29: not in use.
Pin 30: not in use.
The COM connector, as SolaX numbers the pins. Pins 5 and 6 are for external control, pin 26 is GND. The numbers are on the plug.
  • Pin 5 A, REMOTE_485A
  • Pin 6 B, REMOTE_485B
  • Pin 26 GND, GND_COM
03

The cable

A network cable with an RJ45 plug for the dongle at one end and the other end cut off. At the inverter end, only the three wires from pins 4, 5 and 3 are used, with ferrules fitted.

From the dongle to the inverter
Dongle endInverter end
Dongle pin 4, blue (A)COM pin 5, REMOTE_485A
Dongle pin 5, white/blue (B)COM pin 6, REMOTE_485B
Dongle pin 3, white/green (GND)COM pin 26, GND_COM
The other wiresCut off and insulated
04

Settings

On the inverter

Menu > Setting > Advance > Comparameters
Ex485 Modbus Baudrate 9600 and address 1, as from the factory. Advance requires the installer code.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
SolaX, X1-HYB-LV
Connection
By cable (RS485)
RS485 settings
Keep the default: 9600 baud, 8N1, address 1.
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Check the baud rate and address

    On the display, go to Menu, Setting, Advance and Comparameters. This requires the installer code. Ex485 Modbus Baudrate must be set to 9600 and the address to 1, as from the factory.

  2. 2
    Unplug the COM connector

    Switch off the inverter first: switch it off on the display, switch off the AC breaker, set the DC switch to OFF, and switch off the battery. Wait 5 minutes. Unscrew the COM connector, and pull it out. If there's only a dust cover, use the COM connector from the accessory bag.

  3. 3
    Pass the cable through the connector's parts

    Pass the cut end of the cable through the nut, the claws, the seal and the connector housing, in that order.

  4. 4
    Prepare the cable

    Strip 13 mm of the three wires from pin 4 (blue), pin 5 (white/blue) and pin 3 (white/green), and crimp terminals on. Insulate the other wires.

  5. 5
    Put the wires in pins 5, 6 and 26

    Blue (A) goes in pin 5, white/blue (B) in pin 6 and white/green (GND) in pin 26, following the numbers on the connector. Push them in until they click. Don't touch wires already in the other pins: they belong to the energy meter, the current clamp and the battery.

  6. 6
    Put the COM connector back in

    Tighten the nut, plug the connector into COM, and screw it in by hand.

  7. 7
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  8. 8
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  9. 9
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  10. 10
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, SolaX X1-HYB-LV, and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

The COM connector is shared with the energy meter, the current clamp and the battery. Don't move wires already in it.
Pins 7 and 8 are the energy meter's RS485 and pins 17 to 19 the battery's. The dongle goes in 5, 6 and 26.
The Dongle port is for SolaX's own Pocket WiFi. The GridZeno dongle doesn't go in it.
If you aren't used to fitting wires in a terminal connector, let the installer do it.

SolaX X1-HYB-LV-EU isn't on the compatibility list yet. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: SolaX X1-HYB-LV-EU User Manual (EN), The pin table for the 30-pin COM connector (REMOTE_485A and B on pins 5 and 6, GND_COM on pin 26) and Advance, Comparameters.