100 days Free returns on the GridZeno Dongle. Try it on your own system. If it doesn't fit, we take it back and pay the shipping.
Installation · SolaX

Install GridZeno on SolaX X1-Fit.

X1-Fit G4 is SolaX's single-phase battery inverter. It has RS485 on pins 4 and 5 in the RJ45 port COM/LCD, which SolaX has set aside for data collection and external control with Modbus RTU. Pin 3 carries power, so the cable must be made with only the three wires that are needed.

Applies to
X1-Fit-3.7 to 7.5 G4 (W and M)
Connection
Network cable with RJ45 plug
Time
About 25 minutes

The battery is controlled with SolaX' remote control, which stops by itself if the dongle goes silent. What GridZeno can do on SolaX X1-Fit

How the dongle recognises it: The start of the serial number: F43, F450, F460, F475 or PRE is X1-Fit/RetroFit G4. PRI is X1-Fit G3, which is only read.

GridZeno Dongle for SolaX X1-Fit

01

What you need

GridZeno Dongle
The device ID is on the label, e.g. GZ-A1B2C3.
Cable
A network cable that's re-crimped at the inverter end with only three wires.
RJ45 plug and crimping tool
For the inverter end. The waterproof connector piece is in the accessory bag.
USB power
A 5 V USB charger and a cable with USB-C.
02

The port

Among the communication ports on the underside, by Upgrade/Dongle and DRM. BMS, Meter/CT and CAN are next to it. The cable is passed in through the waterproof RJ45 connector piece from the accessory bag.

Port
COM/LCD
Pin 1: Dry contact, Drycontact_A(in).
Pin 2: Dry contact, Drycontact_B(in).
Pin 3: Power, +12V.
Pin 4: A, 485A, blue wire.
Pin 5: B, 485B, white/blue wire.
Pin 6: GND, GND, white/green wire.
Pin 7: Dry contact, Drycontact_A(out).
Pin 8: Dry contact, Drycontact_B(out).
The COM/LCD port, with the pins numbered as SolaX numbers them. Pin 3 carries 12 V and must not be connected. The plug shown with the contacts facing you and the locking tab at the back: pin 1 is furthest to the left.
  • Pin 4 A, 485A
  • Pin 5 B, 485B
  • Pin 6 GND, GND
  • Pin 3 Must not be connected, +12V
03

The cable

A network cable where the inverter end is crimped with only three wires: the dongle's A on pin 4, B on pin 5 and GND on pin 6. The rest of the positions in the plug are empty. An ordinary straight cable must never be used here: it would put the dongle's GND on pin 3, which carries power. The cable has to go through the waterproof connector piece before the plug is crimped on.

From the dongle to the inverter
Dongle endInverter end
Dongle pin 4, blue (A)SolaX pin 4, 485A
Dongle pin 5, white/blue (B)SolaX pin 5, 485B
Dongle pin 3, white/green (GND)SolaX pin 6, GND
The other wiresCut off and insulated, especially the one on pin 3
04

Settings

On the inverter

Menu > Settings > Advanced settings > Modbus > Function Select
COM485, for ordinary Modbus communication
Baud Rate and Address in the same menu
Read them off the screen. The dongle must have the same. The manual's text says 19200 from the factory, but its screenshot shows 115200.

In GridZeno's Welcome

The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.

Manufacturer and model
SolaX, X1-Fit
Connection
By cable (RS485)
RS485 settings
The same baud rate and address as the inverter, 8N1. If the inverter is set to 115200, set it to 19200, and set 19200 on the dongle.
05

Step by step

Each step has a small drawing that shows what to do.

  1. 1
    Check the Modbus menu

    In the display, go to Menu, Settings, Advanced settings, Modbus. It requires the installer code. Function Select must be set to COM485. Note down Baud Rate and Address: the dongle must have the same.

  2. 2
    Pass the cable through the connector piece

    Pass the cable through the waterproof RJ45 connector piece from the accessory bag, and strip 15 mm of the sheath.

  3. 3
    Crimp the inverter end with three wires

    Cut off the plug at the inverter end. Crimp a new plug on with blue (A) on pin 4, white/blue (B) on pin 5 and white/green (GND) on pin 6. The other wires are cut off and insulated.

  4. 4
    Plug it into COM/LCD

    The port is on the underside by Upgrade/Dongle and DRM. Press the plug into the COM/LCD port until it clicks, and tighten the connector piece so the port is sealed.

  5. 5
    Plug the RJ45 end into the dongle

    The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.

  6. 6
    Connect power to the dongle

    Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.

  7. 7
    Connect the dongle to the network

    Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.

  8. 8
    Log in, and choose your inverter

    Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, SolaX X1-Fit, and the connection By cable (RS485). Set the inverter's baud rate and address under RS485 settings. Press Save inverter, and the dongle fetches its setup and reads the inverter.

The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.

06

Take care

Pin 3 in COM/LCD carries 12 V. An ordinary network cable connects all eight pins, so the inverter end must be crimped with only the three wires.
Use only COM/LCD. Meter/CT is the energy meter's port, BMS the battery's, and Upgrade/Dongle is for SolaX's own monitoring dongle. CAN also has RS485 on pins 1 and 2, but it's for parallel operation and not for the dongle.
Pins 1, 2, 7 and 8 are dry contacts, for example for SolaX's Adapter Box and a heat pump. If there's already a cable in COM/LCD, write to us before you connect the dongle.
COM/LCD isn't a network port. Never plug it into a router or switch.

What GridZeno can control on SolaX X1-Fit, and how, is on the page about SolaX X1-Fit. If you're stuck, write to us with the model name.

07

Source

Ports, pins and menus are from the manufacturer's own manual: SolaX X1-Fit-G4 3.7 kW / 5.0 kW / 6.0 kW / 7.5 kW Installation Manual, version 3.0 (2024-08-01), Sections 6.4.4, COM Communication (COM PIN Definition), 6.4.5, Communication Connection Steps, and Advanced settings, 7) Modbus.