Install GridZeno on Growatt WIT 50-100K.
WIT 50-100K is Growatt's large three-phase inverter, which stands on the floor or hangs on the wall. The communication is in a panel on the right side, behind a cover. The dongle is connected with two wires in the 16-pin connector COM1, pins 3 and 4, which Growatt has set aside for external communication.
- Applies to
- WIT 50-100K-A, -H, -AU and -HU
- Connection
- Wires in the inverter's terminal plug
- Time
- About 30 minutes
Controlled like the Growatt WIT: charging and holding with the inverter's operating mode, selling with Growatt's VPP protocol. The dongle always sets the inverter's own mode back afterwards. What GridZeno can do on Growatt WIT 50-100K
How the dongle recognises it: The type code 5600 or 5601, or 5603 with a rated power above 15 kW. 5600 appears only in the Home Assistant integration Growatt_ModbusTCP, not in Growatt's own documents, and the sources disagree on which WIT 5601 is.
What you need
- GridZeno Dongle
- The device ID is on the label, e.g. GZ-A1B2C3.
- Cable
- GridZeno's Modbus cable with one end cut off, or another network cable with one plug.
- The 16-pin connector
- From the inverter's accessory bag, and a short wire for the bridge between pins 5 and 10.
- Tools
- Screwdriver for the right cover, and wire strippers.
- USB power
- A 5 V USB charger and a cable with USB-C.
The port
In the panel on the inverter's right side, behind the right cover, together with BMS-COM (16-pin), COM2 (30-pin), the USB box and DRMS. The matching connector is in the accessory bag.
- Port
- COM1 (16-pin connector)
- Pin 3 A, RS485A1
- Pin 4 B, RS485B1
The cable
A network cable with an RJ45 plug for the dongle at one end and the other end cut off. At the inverter end, only the two wires from pins 4 and 5 are used. Also a short wire that makes a bridge between pins 5 and 10 in the COM1 connector.
| Dongle end | Inverter end |
|---|---|
| Dongle pin 4, blue (A) | COM1 pin 3, RS485A1 |
| Dongle pin 5, white/blue (B) | COM1 pin 4, RS485B1 |
| Short wire | Bridge between COM1 pin 5 and pin 10 |
| The other wires | Cut off and insulated |
Settings
On the inverter
- Communication address
- 1, as from the factory. It's only changed with Growatt's ShineBus, by an installer.
- Modbus
- Modbus RTU at 9600 baud, 8N1. That's what the dongle uses from the factory, so there's nothing to set.
In GridZeno's Welcome
The inverter is chosen in GridZeno: in Welcome the first time, and later under System, Change inverter. The dongle fetches its setup from there.
- Manufacturer and model
- Growatt, WIT over 15 kW
- Connection
- By cable (RS485)
- RS485 settings
- Keep the default: 9600 baud, 8N1, address 1.
Step by step
Each step has a small drawing that shows what to do.
- 1Switch off the inverter, and remove the right cover
Send a shutdown command in the app or on the website first. Then turn off the battery's switch and breaker, then the breaker between the grid and the inverter, and set the DC switches to OFF. Unscrew the right cover so you can see the communication panel.
- 2Remove the dust cap from COM1
COM1 is the 16-pin connector in the panel on the right side, between BMS-COM and the large 30-pin COM2. Remove the dust cap.
- 3Prepare the cable
Pass the cable in through the hole in the sealing pad, and strip the two wires from pin 4 (blue) and pin 5 (white/blue). Insulate the other wires.
- 4Put the wires in pins 3 and 4
Blue (A) goes in pin 3 and white/blue (B) in pin 4 of the 16-pin connector from the accessory bag, following the numbers on the connector. Make a bridge with a short wire between pin 5 and pin 10. That switches on the RS485 resistor, as Growatt specifies when an external device controls the inverter.
- 5Plug the connector into COM1
Plug the connector into COM1 so it sits firmly and tightly. Put the right cover back on once all connections have been checked.
- 6Plug the RJ45 end into the dongle
The cable's other end goes into the dongle's RS485 port. Place the dongle somewhere dry and close to the inverter, so the cable doesn't hang from the plug.
- 7Connect power to the dongle
Plug the USB-C cable into the dongle and the charger into a socket. The dongle starts by itself. It gets power from the charger, not from the inverter.
- 8Connect the dongle to the network
Over Wi-Fi: the first time, the dongle creates its own Wi-Fi, GridZeno-Setup- followed by the last characters of the device ID. Connect your phone to it, choose your own network, enter the password, and press Save and connect. When it says Connection OK, press Go to GridZeno. Over cable (LAN): plug a network cable from the router into the dongle's network port.
- 9Log in, and choose your inverter
Log in to GridZeno. Welcome pairs the dongle with its device ID. Then choose your inverter, Growatt WIT, and the connection By cable (RS485). Press Save inverter, and the dongle fetches its setup and reads the inverter.
The dongle's own setup is described with screenshots in The user guide, and the pairing in Getting started.
Take care
What GridZeno can control on Growatt WIT 50-100K, and how, is on the page about Growatt WIT 50-100K. If you're stuck, write to us with the model name.
Source
Ports, pins and menus are from the manufacturer's own manual: Growatt WIT 50-100K Storage/Hybrid Inverter User Manual (GR-UM-299-A-03, EN, 2026-03), Section 3.1, Overview, 6.1, figure 6.1, 6.5.2, External Communication Connection, with table 6.4, and 7.2.1, Set the Communication Address.